11.. . APPENDIX A: MASTER ICON FILE REFERENCE
USING THE OMP-MODL11-34
+5 VOLT OUTPUT ICON (SYSTEM BASE)
FUNCTION:
A regulated 5Vdc, 125mA current limited output is provided as an integral part of the
OMP-MODL System Base. The + 5 Volt icon provides software access to this alarm
output.
INPUTS:
Data/Logic Signal: Logic type. True input turns Output ON. LOW input turns Output
OFF. Optionally, use the Latch icon in front of the icon to latch the Output
ON upon receipt of a momentary True input.
Update Clock: None
Enable: None
OUTPUTS:
Output Signal: Hardware output only. No output terminal shown on icon for
Program Net connections.
ICON CONFIGURATION DIALOG BOX:
CONFIGURATION OPTIONS:
Icon Name:Specify the label for the icon. This name will show directly under the icon
within the Program Net.
Input Name: In this box, HyperNet displays the Output Name of the icon connected to
this icon’s Input. The Output Name can be changed in the other icon’s
dialog.