11.. . APPENDIX A: MASTER ICON FILE REFERENCE
USING THE OMP-MODL11-92
STOP LOGGING FUNCTION ICON
When the Stop Logging icon receives a Logic True input, it stops the OMP-MODL
execution of the Program Net. The function is the same as if the front panel STOP
button were pressed.
In the following example Net, if the flow ever drops to less than 10GPH, the OMP-MODL
will stop logging. In this Net, logging will not restart, even if the flow increases to over
10GPH again.
INPUTS:
Data/Logic Signal: Logic type (True/False). A True signal on this input Stops
execution of the OMP-MODL Program Net..
Enable: Processing of the icon is allowed when the Enable pin is
unconnected or when connected and Enable signal is TRUE.
OUTPUTS:
Output Signal: Internal system control output only. No output terminal shown on
icon for Program Net connections.
ICON CONFIGURATION DIALOG BOX:
No Configuration Dialog is provided.