11.. . APPENDIX C: HYPERWARE FILE LISTING
USING THE OMP-MODL11-112
High Speed Thermocouple Application:
In some applications, maximum speed of thermocouple measurement is desired.
The Thermocouple icon is one of the slowest to process in a Program Net due to the
intensive math associated with each sample. A Cold Junction Compensation
reading is required as well as the thermocouple reading, then the two are combined
through curve approximating polynomials... heavy math for the OMP-MODL.
A method to improve on the throughput rate of thermocouple inputs exists. If the
thermocouple inputs are read as mV signals (which are processsed very quickly) and
the CJC is read as a resistance (which is lots faster than temperature), the net will
process many times faster. The mV readings from the Thermocouple icon and the
resistance reading from the CJC icon are then merged in a Post-Processing Net and
the results (in degrees) are put into a destination *.HLD file for plotting.
The following Program Net represents an application of this method of high speed
thermocouple temperature data collection. Temperature rise data on components
within an automobile brake is desired. Thermocouples are installed and connected
to OMP-MODL input channels configured as mV inputs. The CJC input is sent to
memory in units of OHMS.
A unique triggering scheme is implemented with the Event icon and three Sample
Rate Clocks. One Sample Rate Clock causes the Event icon to sample the status of
a switch connected to the brake pedal every 10mS. When the switch is open (ie
brakes NOT activated) the CJC icon is enabled and the Sample Rate Clock sends a
reading to memory every second. Additionally,. the 50mS Sample Rate Clock is
sampling at its primary rate which is set to 1 second.
When the brake pedal is depressed, the CJC icon is disabled and the 50mS Sample
Rate Clock driving the three Voltage icons (thermocouple inputs) switches to its
Alternate rate, storing readings to memory every 50mS.
After the data has been collected and downloaded to the PC, a Post-Processing Net
is constructed as shown in the following diagram.